Please use this identifier to cite or link to this item: http://localhost:8080/xmlui/handle/123456789/5264
Full metadata record
DC FieldValueLanguage
dc.contributor.authorMohammed K. Mohammed, Abdulsattar H. Jasim-
dc.date.accessioned2022-10-22T19:01:43Z-
dc.date.available2022-10-22T19:01:43Z-
dc.date.issued2021-03-12-
dc.identifier.issn0011-9342-
dc.identifier.urihttp://localhost:8080/xmlui/handle/123456789/5264-
dc.description.abstractShort circuit (S.C) analysis helps to select, control, and coordinate protection equipment like fuses, circuit breakers, relays, and transformers. This paper presents a simulation and analysis of 132 KV Substation in Ramadi city. Which includes power flow analysis and short circuit analysis in the ETAP Software (Electrical Transient Analyzer Program). Various types of faults are simulated for many buses in the tested substation using ANSI and IEC standards. Different scenarios were used for the connection of substations transformers, to evaluate the maximum and minimum current and short circuit level. The magnitude of S.C for the system under study in which all the transformers connected in individuals are considered as a reference to other connections. Finally, the simulation results for IEC and ANSI is presented to ensure reliable and valid results.en_US
dc.language.isoenen_US
dc.publisherDesign Engineeringen_US
dc.subjectETAPen_US
dc.subjectANSIen_US
dc.subjectIECen_US
dc.subjectShort circuit analysisen_US
dc.subjectLoadflowen_US
dc.titleFault Diagnosis of 132 KV Substation Secondary System based on Association Analysis using ETAPen_US
dc.typeArticleen_US
Appears in Collections:مركز بحوث الطاقة المتجددة